An Illinois dialysis center has to clear three sets of rules before it treats a patient: state review of the project, federal design and water standards for Medicare-certified facilities, and the state plumbing code. The projects that stay on schedule settle all three during planning, before the first wall goes up. We build dialysis centers as a general contractor, and this guide walks through each requirement in the order you will meet it.
Key Takeaways
- Illinois requires a permit or exemption from the Health Facilities and Services Review Board before you build, modify or establish a dialysis center. As of July 1, 2026, the capital expenditure minimum that triggers a certificate of need permit is $4,779,437 for dialysis centers.
- Federal rule 42 CFR 494.60 governs the physical environment: patient visibility, cross-contamination control, emergency access and life safety.
- The water system is the most specialized part of the build: continuous loop piping, no dead ends, bacteria and endotoxin limits, and a state plumbing code with its own backflow and signage rules.
- A new facility, a relocation and a renovation of an occupied center face different review paths, so settle the scope and phasing with your contractor before you file.
Table of Contents
- Step one: state review by the Health Facilities and Services Review Board
- Step two: the federal physical environment rule
- Step three: the water treatment and distribution system
- Step four: new facility, relocation or renovation
- How the requirements show up in the build
- What a dialysis buildout asks of a general contractor
- Planning checklist before you file or bid
- FAQ
Step one: state review by the Health Facilities and Services Review Board
Illinois' Health Facilities Planning Act requires a permit or exemption from the Health Facilities and Services Review Board (HFSRB) before anyone constructs, modifies or establishes a health care facility. The Act expressly covers kidney disease treatment centers, including free-standing hemodialysis units certified under 42 CFR Part 494. In practice, a new center, a relocation or a significant change to an existing one starts here, not with a building permit.
The HFSRB is an independent nine-member commission appointed by the Governor. A permit needs affirmative votes from a majority of its voting members, and IDPH's Division of Health Systems Development provides staff support, according to the Board's program page. Facilities operated by the federal government are not subject to the Act.
What triggers a certificate of need permit
Under 77 Ill. Admin. Code 1130.310, a permit is required for projects that:
- establish a health care facility;
- exceed the capital expenditure minimum;
- substantially change scope or functional operation;
- change bed capacity or ownership;
- involve acquiring major medical equipment.
The dollar threshold is adjusted every year. The HFSRB's schedule effective July 1, 2026 sets the minimum at $4,779,437 for applicants other than hospitals and long-term care facilities, which includes dialysis centers, with the same figure applying to major medical equipment. Check the Board's page for the figure in force when you file, since it resets each year.
For scale, look at what real applications cost. A 2024 application by Dialysis Care Center to relocate its Oak Lawn in-center hemodialysis facility, approved for 14 stations, carried an estimated cost of $5,403,927. A relocation is also a good reminder that a project can need review for reasons beyond the dollar figure: the move itself changes where the service is provided.
Reporting once you hold a permit
A permit comes with obligations that shape your construction schedule. Under the Act, the holder must file annual progress reports around each anniversary of Board approval and a final completion and cost report within 90 days after the approved completion date. The project may not exceed the approved permit amount by more than the limit set in Board rules. Change orders and finish upgrades therefore matter to your compliance, not only your budget. A contractor who tracks cost against the permit amount from day one keeps those reports simple.
Step two: the federal physical environment rule
Medicare-certified dialysis facilities answer to 42 CFR 494.60, the Conditions for Coverage on physical environment. It requires the facility to be designed, constructed, equipped and maintained to provide a safe, functional and comfortable treatment environment. For layout, three requirements matter most:
- Treatment space. Each patient's space must be large enough to provide needed care, prevent cross-contamination, and accommodate emergency equipment and staff.
- Visibility. Patients must be in view of staff during hemodialysis. This drives how the treatment floor is arranged and where nurse stations, columns and partitions can go.
- Privacy. Where an exam or treatment requires body exposure, the plan must provide privacy accommodations.
Life safety and site
The same section ties life safety to the building. A facility without one or more exits to the outside at grade level from the patient treatment area must comply with the NFPA 101 Life Safety Code provisions for Ambulatory Health Care Occupancies, regardless of patient count. That matters for second-floor suites in medical office buildings, a common Chicago-area setting. The rule also bars a dialysis facility from operating in a building adjacent to an industrial high-hazard area.
Design guidance
The Facility Guidelines Institute's guidelines for outpatient facilities include a dedicated section titled Specific Requirements for Renal Dialysis Centers, covering patient care accommodations, examination spaces and related design elements. Your architect will work from the edition Illinois has adopted and your local building department enforces, so confirm the edition with them early. Municipal codes in Chicago and the suburbs add their own permit reviews on top, which is why a general contractor who knows the local building departments saves weeks.
Step three: the water treatment and distribution system
Dialysis patients are exposed to large volumes of water through the dialysate, so water quality rules are strict and they shape the mechanical rough-in.
Federal standards
42 CFR Part 494 requires water and equipment to meet the AAMI dialysate standard ANSI/AAMI RD52:2004. The water treatment system must include a carbon component that removes chlorine and chloramine, plus a backup component or a second carbon tank in series.
CMS's State Operations Manual Appendix H (issued February 21, 2020) sets the surveyor guidance on the distribution piping:
- The product water loop must be continuous.
- Minimum flow velocity is 3 ft/sec in the distal portion of an indirect feed loop and 1.5 ft/sec for direct feed.
- Dead-end pipes must be eliminated.
- Piping materials must not contribute aluminum, copper, lead or zinc to the water.
The same document sets bacteriology below 200 CFU/mL and endotoxin below 2 EU/mL, tested at least monthly. After a newly installed or modified distribution system, testing is weekly for one month. That last point belongs in your construction schedule: the system must be commissioned and tested before the first patient, so water testing time sits between substantial completion and opening.
CMS also requires that water distribution systems be disinfected at least monthly, or more often if the manufacturer's frequency calls for it. Design for that: valves, access points and sample ports have to be where the technicians can reach them.
The Illinois Plumbing Code
The state adds its own requirements in Section 890.740 of the Illinois Plumbing Code, amended effective April 24, 2014:
| Item | Requirement |
|---|---|
| Water supply inlet to dialysis equipment | Reduced-pressure backflow preventer (ASSE 1013) or fixed air gap |
| Reuse-room or repair-room water supplies | Isolated from other DI/RO lines by RPZ or air gap |
| Sinks fed by DI/RO water | 8x10-inch sign above, reading "This Water For Dialysis Only" |
| Waste | Individual indirect waste connections, with individually trapped and vented stand pipes for each dialysis unit |
These are small line items on a drawing and expensive to fix after drywall. Individually trapped and vented stand pipes for each unit, for example, affect wall thickness and ceiling coordination at every chair.
Step four: new facility, relocation or renovation
The path depends on what you are doing.

New facility. You need the HFSRB permit first, then building permits, construction, water system commissioning and testing, and the federal certification steps your operator or consultant manages. The scope is a full buildout: demolition or shell conversion, mechanical, plumbing, electrical, finishes and equipment installation.
Relocation. Because relocations are reviewed as projects in their own right, as the Oak Lawn application shows, plan for review time in addition to construction time. A tight lease expiration at the old site is the usual source of pressure.
Renovating an operating center. Patients still need treatment while you work. The treatment floor, water room and distribution loop all have to be phased so shifts continue, and any change to the distribution system triggers the weekly testing period described above. Phasing, dust control and infection-control barriers are as important as the finishes. Our guide to renovating an occupied commercial building in Illinois covers that phasing approach, and the logic carries over to healthcare floors.
Whether your project crosses a certificate of need threshold, needs only an exemption, or needs neither depends on its facts. Your operator's counsel or regulatory consultant should confirm that with the HFSRB staff before you commit to a schedule.
How the requirements show up in the build
A dialysis buildout is not an ordinary medical office. Here is where the rules above land on the construction schedule:
- Programming and design. Station count, sightlines to every chair, emergency equipment clearances, privacy for exams and patient entrances determine the plan.
- Water room and loop. The RO equipment location, carbon tanks in series, loop routing without dead legs and sampling points need coordination between the mechanical, plumbing and equipment trades.
- Plumbing rough-in. Backflow protection, indirect waste and trapped, vented stand pipes at each unit all have to be placed before walls close.
- Life safety. Exits, rated assemblies and fire alarm work follow the occupancy classification.
- Commissioning and testing. The water system is disinfected and tested before opening, with the weekly testing period after a new or modified system.
- Closeout. Final completion and cost documentation lines up with the permit reporting.
Budgeting follows the same logic. Water treatment, plumbing and infection-control finishes push the per-square-foot cost beyond a standard office. Our medical facility construction cost guide explains how to set a budget for this kind of work.
What a dialysis buildout asks of a general contractor

The project mixes healthcare-specific engineering with tight trade coordination, and the party that coordinates it carries the schedule. Expert Building Maintenance, Inc. (EBM) is a commercial general contractor in Burr Ridge, Illinois, established in 2001, that builds dialysis centers and works across healthcare, skilled nursing and office projects. We manage projects from initial planning and demolition through construction and final turnover, with project management and trade coordination in house, and we specialize in renovating occupied buildings while coordinating work to limit disruption to daily operations.
If you are weighing a new center, a relocation or an upgrade to an existing one, our team can walk through scope and sequencing with you. See our services or recent projects, or contact us through ebmchicago.com.

Planning checklist before you file or bid
- Confirm with HFSRB staff whether your project needs a permit or exemption, using the capital expenditure minimum in force at filing.
- Fix the station count and the treatment floor layout against the visibility, privacy and emergency equipment rules.
- Check whether the space has an exit to the outside at grade from the treatment area, which decides whether NFPA 101 ambulatory health care provisions apply.
- Specify the water system to the AAMI standard, with carbon tanks in series and a continuous loop without dead ends.
- Draw the Illinois plumbing code items (backflow protection, signage, indirect waste) into the plans.
- Put water testing and commissioning on the schedule between construction and opening.
- Track cost against the permit amount from the first change order.
FAQ
Do I need state approval to build a dialysis center in Illinois?
Yes. The Health Facilities Planning Act requires a permit or exemption from the HFSRB before constructing, modifying or establishing a health care facility, and it names free-standing hemodialysis units among the covered facilities. Whether you need a full permit or an exemption depends on the project's scope and cost.
What is the cost threshold for a certificate of need permit?
As of July 1, 2026, the HFSRB's capital expenditure minimum for applicants other than hospitals and long-term care facilities, including dialysis centers, is $4,779,437. The Board adjusts it annually, so check its program page for the figure in force when you file.
What are the water quality limits for a dialysis center?
CMS guidance sets bacteria below 200 CFU/mL and endotoxin below 2 EU/mL, tested at least monthly. A new or modified distribution system is tested weekly for one month. The system must also be disinfected at least monthly.
What does the Illinois Plumbing Code require for dialysis equipment?
Section 890.740 requires a reduced-pressure backflow preventer or fixed air gap on the water inlet to dialysis equipment. It also requires a "This Water For Dialysis Only" sign above DI/RO-fed sinks and individually trapped and vented stand pipes with indirect waste for each unit.
Can a dialysis center be renovated while it stays open?
Yes, with phasing that keeps treatment shifts running and protects patients from construction. Any change to the water distribution system triggers the follow-up testing period, so build that into the schedule.